Heat-Chain Commercial Hydronic Heating
Heat-Chain™ is a modular, high-efficiency hydronic heating solution designed for commercial water heating in multifamily buildings and businesses. Powered by the HP80 gas absorption heat pump (1.4 CoP / 140% AFUE), it operates on natural or LP gas and delivers reliable, low-emission performance. The system is available in two skid-mounted configurations—HC80-2x (160K BTU/hr) and HC80-3x (240K BTU/hr)—for simplified transport, installation, and scalability. Each skid includes factory-mounted components and consolidated connections for gas, power, condensate, and hydronic fluid, streamlining setup and reducing on-site labor.
Integrated System Design and Connectivity Features of Heat-Chain™
- 100% External Control: Compatible with third party system controllers for full modulation across units. Ensures balanced runtime—no single HP80 operates more than others.
- Unified Connectivity: Units can be grouped together in the Anesi APP for simplified monitoring.
- Redundant Communication: Each HP80 retains its own cellular signal—no single point of failure.
- Simplified Gas Connection: One 1-1/4” inlet splits to individual HP80 units; sized by skid gas line length.
- Hydronic Integration: Single 1.5” inlet/outlet transitions to 1” lines upstream of pumps to maintain even load distribution.
- Condensate Management: Individual ⅜” drains merge into 1” PEX-B main line with slope and optional heat trace; skid must be level. Ground clearance 24” to PEX-B connection.
- Dedicated Pumps: Each HP80 includes an enclosed hydronic pump (target 8.5 GPM).
- Skid-Mounted Design: Entire system on one skid for easy transport, installation, and service access.
- Optional Electrical Integration: Pre-wired single-point bulkhead connection for power and control to each HP80.

Modular Hydronic Heating with Heat-Chain™ for Commercial Applications

Heat-Chain™ is a flexible, high-efficiency hydronic heating solution engineered for a wide range of commercial environments. From multi-family housing and senior living facilities to laundromats, fitness centers, and small office buildings, Heat-Chain™ delivers reliable, low-emission heating with simplified installation and scalable performance. Built around the HP80 gas absorption heat pump (1.4 CoP / 140% AFUE), the system operates on natural or LP gas and is available in two skid-mounted models—HC80-2x (160K BTU/hr) and HC80-3x (240K BTU/hr). Each unit arrives pre-assembled with integrated components and consolidated connections for gas, power, condensate, and hydronic fluid, minimizing on-site labor and accelerating deployment. Whether you’re retrofitting an existing system or designing a new build, Heat-Chain™ offers a modular approach to commercial water heating that meets modern efficiency and sustainability standards.
Specifications
| TECHNICAL DATA | UNIT | HC80-2X | HC80-3X |
|---|---|---|---|
| Heating Output* | BTU/h | 156000 | 234000 |
| CoP (Higher Heating Value)* | 1.43 | 1.43 | |
| Max Return Temp (at full fire) | ° F/C | 132/55.6 | 132/55.6 |
| Gas Input (Higher Heating Value)* | BTU/h | 109000 | 163500 |
| Modulation (fully variable) | 8:1 | 12:1 | |
| Combustion | Condensing | Condensing | |
| NOx Compliance (Ultra-Low NOx) | ng/J | <14 | <14 |
| GHP Hydronic Flow (min) | gpm/lpm | 7/26.5 | 7/26.5 |
| GHP Hydronic Flow (max) | gpm/lpm | 10/37.9 | 10/37.9 |
| Ambient Temp (min-max) | ° F/C | -40 to 130/-40 to 54 | -40 to 130/-40 to 54 |
| Voltage | VAC | 115 | 115 |
| Current (max) | Amp | 14 | 21 |
| Length | in/cm | 86/218.4 | 138/350.5 |
| Width | in/cm | 72/182.9 | 72/182.9 |
| Height | in/cm | 51/129.5 | 51/129.5 |
| Height with Flue | in/cm | 63/160 | 63/160 |
| Hydronic Connection FNPT | in | 1-1/2 | 1-1/2 |
| Gas Connections MNPT | in | 1-1/4 | 1-1/4 |
| Condensate Connection, Type B | in | 1 | 1 |
| Refrigerant | R717 | R717 | |
| CTA2045 Compliance | Future Release | Future Release | |
| Communications Capabilities | Cellular | Cellular | |
| Certification | ETL per ANSI Z21.40.1/CGA 2.91 | ETL per ANSI Z21.40.1/CGA 2.91 |
*Performance at standard ANSI rating conditions of 47°F ambient, 95°F return